Conduit fill is the percentage of a conduit's interior cross-sectional area occupied by conductors. NEC Chapter 9, Table 1 limits fill to 40% for 3 or more conductors, 31% for 2 conductors, and 53% for a single conductor — these maximums ensure cables can be pulled without jacket damage and allow heat to dissipate. This calculator was built by licensed low-voltage professionals following NEC Chapter 9 fill rates and NFPA 70 standards. Wire outside diameter data is sourced directly from manufacturer specifications. Covers THHN conductors, Cat5e/Cat6/Cat6A, fire alarm cable, and fire-rated sleeves (STI EZPath, Hilti) in EMT, RMC, and PVC Schedule 40/80.
Built by BICSI Corporate Members with 15+ years of low-voltage installation experience across Florida. Calculations comply with NFPA 70 (NEC) Chapter 9.
Estimates based on NEC, NFPA, and IEEE standards. For reference only. Consult a licensed professional for critical design decisions.
Sleeve and Conduit Fill Tool
Free, NEC-compliant conduit fill calculator for electricians, low-voltage technicians, estimators, and engineers. Determine how many wires or cables safely fit inside various conduit types.
Select your conduit and cables, then click Calculate
NEC Wire Fill Chart by Conduit Size
Maximum THHN/THWN conductor count per conduit size at 40% fill — NEC Chapter 9, Table C values.
| AWG | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 12 | 22 | 35 | 61 | 84 | 138 | 241 | 364 | 476 | 608 |
| 12 AWG | 9 | 16 | 26 | 45 | 61 | 101 | 176 | 266 | 347 | 443 |
| 10 AWG | 5 | 10 | 16 | 28 | 38 | 63 | 111 | 167 | 219 | 279 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 36 | 64 | 96 | 126 | 161 |
| 6 AWG | 2 | 4 | 7 | 12 | 16 | 26 | 46 | 69 | 91 | 116 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 28 | 43 | 56 | 71 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 24 | 36 | 47 | 60 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 20 | 30 | 40 | 51 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 15 | 22 | 29 | 37 |
Source: NEC 2020, Table C1 — THHN/THWN-2 conductors. Values are for 3+ conductors (40% fill). Always verify against your locally adopted NEC edition.
| AWG | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 13 | 22 | 36 | 63 | 85 | 140 | 200 | 309 | 412 | 531 |
| 12 AWG | 9 | 16 | 26 | 46 | 62 | 102 | 146 | 225 | 301 | 387 |
| 10 AWG | 6 | 10 | 17 | 29 | 39 | 64 | 92 | 142 | 189 | 244 |
| 8 AWG | 3 | 6 | 9 | 16 | 22 | 37 | 53 | 82 | 109 | 140 |
| 6 AWG | 2 | 4 | 7 | 12 | 16 | 27 | 38 | 59 | 79 | 101 |
| 4 AWG | 1 | 2 | 4 | 7 | 10 | 16 | 23 | 36 | 48 | 62 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 41 | 53 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 17 | 26 | 34 | 44 |
| 1 AWG | 1 | 1 | 1 | 4 | 5 | 8 | 12 | 19 | 25 | 33 |
Source: NEC 2020, Table C8 — THHN/THWN-2 conductors. Values are for 3+ conductors (40% fill). Always verify against your locally adopted NEC edition.
| AWG | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 11 | 21 | 34 | 60 | 82 | 135 | 193 | 299 | 401 | 517 |
| 12 AWG | 8 | 15 | 25 | 43 | 59 | 99 | 141 | 218 | 293 | 377 |
| 10 AWG | 5 | 9 | 15 | 27 | 37 | 62 | 89 | 137 | 184 | 238 |
| 8 AWG | 3 | 5 | 9 | 16 | 21 | 36 | 51 | 79 | 106 | 137 |
| 6 AWG | 1 | 4 | 6 | 11 | 15 | 26 | 37 | 57 | 77 | 99 |
| 4 AWG | 1 | 2 | 4 | 7 | 9 | 16 | 22 | 35 | 47 | 61 |
| 3 AWG | 1 | 1 | 3 | 6 | 8 | 13 | 19 | 30 | 40 | 51 |
| 2 AWG | 1 | 1 | 3 | 5 | 7 | 11 | 16 | 25 | 33 | 43 |
| 1 AWG | 1 | 1 | 1 | 3 | 5 | 8 | 12 | 18 | 25 | 32 |
Source: NEC 2020, Table C10 — THHN/THWN-2 conductors. Values are for 3+ conductors (40% fill). Always verify against your locally adopted NEC edition.
| AWG | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 9 | 17 | 28 | 51 | 70 | 118 | 170 | 265 | 358 | 464 |
| 12 AWG | 6 | 12 | 20 | 37 | 51 | 86 | 124 | 193 | 261 | 338 |
| 10 AWG | 4 | 7 | 13 | 23 | 32 | 54 | 78 | 122 | 164 | 213 |
| 8 AWG | 2 | 4 | 7 | 13 | 18 | 31 | 45 | 70 | 95 | 123 |
| 6 AWG | 1 | 3 | 5 | 9 | 13 | 22 | 32 | 51 | 68 | 89 |
| 4 AWG | 1 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 42 | 54 |
| 3 AWG | 1 | 1 | 3 | 5 | 7 | 12 | 17 | 26 | 35 | 46 |
| 2 AWG | 1 | 1 | 2 | 4 | 6 | 10 | 14 | 22 | 30 | 39 |
| 1 AWG | — | 1 | 1 | 3 | 4 | 7 | 10 | 16 | 22 | 29 |
Source: NEC 2020, Table C11 — THHN/THWN-2 conductors. Values are for 3+ conductors (40% fill). Always verify against your locally adopted NEC edition.
Fire-Rated Sleeve Fill Chart
Maximum cable count per fire-rated sleeve by cable outside diameter. These are UL-tested manufacturer values — not NEC area calculations.
| Cable OD | EZD22 | EZD33 | EZD44+ |
|---|---|---|---|
| 0.118"22/2 | 80 | 352 | 868 |
| 0.138"22/4 | 63 | 266 | 648 |
| 0.157"18/2 | 42 | 192 | 483 |
| 0.177"18/4 | 35 | 154 | 378 |
| 0.197"Cat5e UTP | 30 | 130 | 304 |
| 0.217"8 AWG THHN | 20 | 108 | 255 |
| 0.236"Cat6 UTP | 20 | 88 | 210 |
| 0.256"6 AWG THHN | 12 | 70 | 168 |
| 0.276"Cat6a STP | 12 | 63 | 156 |
| 0.315"Cat6a UTP | 9 | 48 | 110 |
| 0.354"Cat8 | 6 | 35 | 90 |
| 0.394"Composite | 6 | 30 | 72 |
| 0.433"Shielded Comp. | 4 | 24 | 56 |
| 0.492"6-str Armor Fiber | 4 | 20 | 42 |
| 0.591"12-str Armor Fiber | 2 | 12 | 30 |
| 0.709"24-str Armor Fiber | 1 | 6 | 20 |
| 0.787"48-str Armor Fiber | 1 | 6 | 16 |
| 0.984"48-str Armor Fiber | 1 | 4 | 9 |
| 1.181"72-str Armor Fiber | — | 2 | 6 |
| 1.378"1000 kcmil | — | 1 | 4 |
Source: STI EZPath cable transit data. EZD22/EZD33/EZD44+ device sizes. UL tested values.
| Cable OD | Speed 2" | Speed 4" | Modular S | Modular M | Modular L |
|---|---|---|---|---|---|
| 0.118"22/2 | 163 | 819 | 180 | 486 | 1188 |
| 0.138"22/4 | 121 | 596 | 144 | 368 | 851 |
| 0.157"18/2 | 88 | 451 | 112 | 280 | 660 |
| 0.177"18/4 | 69 | 356 | 84 | 216 | 522 |
| 0.197"Cat5e UTP | 56 | 287 | 66 | 176 | 416 |
| 0.216"8 AWG THHN | 45 | 240 | 50 | 150 | 360 |
| 0.236"Cat6 UTP | 37 | 199 | 45 | 117 | 286 |
| 0.256"6 AWG THHN | 32 | 164 | 32 | 96 | 240 |
| 0.275"Cat6a STP | 27 | 141 | 28 | 88 | 198 |
| 0.314"Cat6a UTP | 19 | 109 | 28 | 70 | 160 |
| 0.354"Cat8 | 16 | 85 | 18 | 54 | 126 |
| 0.394"Composite | 13 | 61 | 15 | 40 | 104 |
| 0.433"Shielded Comp. | 11 | 50 | 10 | 35 | 84 |
| 0.491"6-str Armor Fiber | 7 | 38 | 8 | 24 | 60 |
| 0.59"12-str Armor Fiber | 5 | 26 | 6 | 15 | 40 |
| 0.708"24-str Armor Fiber | 3 | 19 | 3 | 12 | 28 |
| 0.786"48-str Armor Fiber | 2 | 14 | 2 | 8 | 24 |
| 0.983"48-str Armor Fiber | 1 | 8 | 2 | 6 | 15 |
| 1.179"72-str Armor Fiber | 1 | 7 | 1 | 2 | 8 |
| 1.375"1000 kcmil | 1 | 3 | — | 2 | 6 |
Source: Hilti published cable capacity data. Speed Sleeve (2"/4") and Modular Sleeve (S/M/L) sizes. Manufacturer tested values.
NEC Chapter 9 Fill Rules
Conduit fill is calculated using cross-sectional area only. NEC limits are intentionally conservative to account for real-world installation variables and heat dissipation. Formula: (Total conductor area / Conduit internal area) x 100.
1 conductor
2 conductors
3+ conductors
Short nipples (≤24")
NEC Conduit Fill Table & Reference Guide
In-depth guidance from licensed low-voltage professionals on NEC fill requirements, common mistakes, and fire-stopping considerations.
EMT, PVC & RMC Conduit Fill Best Practices
EMT, PVC & RMC Conduit Fill Best Practices
NEC fill limits exist to protect cable integrity and ensure safe, reliable installations. Staying well below the maximum fill percentage (ideally at 30-35% for runs longer than 50 feet) reduces pulling tension on cable jackets, prevents heat buildup that degrades performance over time, and leaves room for future cable additions without re-running conduit.
Overfilled conduit creates excessive friction during cable pulls that can stretch conductors, damage insulation, and compromise fire ratings on plenum and riser cables. Plan your conduit sizing based on the total cable capacity you expect over the life of the building, not just the initial installation.
The cost difference between a 1-inch and 1.25-inch conduit is negligible compared to the expense of pulling a new conduit run later. Use pull boxes at intervals of no more than 100 feet and at every second 90-degree bend to reduce cumulative pulling tension.
For raceway-specific tools: EMT conduit fill calculator or PVC Schedule 40/80 calculator.
Common Conduit Fill Table & Calculation Mistakes
Common Conduit Fill Table & Calculation Mistakes
The most frequent mistake is using conductor diameter instead of overall cable outside diameter (OD) for fill calculations. A Cat6a cable with 23 AWG conductors has a conductor diameter of about 0.023 inches, but the full cable OD including jacket is approximately 0.30 inches, over 13 times larger. Always use the cable OD, which includes all insulation layers and the outer jacket.
Another common error is mixing cable types without recalculating fill percentage. Adding a few fire alarm cables to a conduit already near capacity with data cables can push you over the NEC limit. Forgetting that the 40% fill rule only applies to three or more conductors is also frequent: two conductors are limited to 31%, and a single conductor allows 53%.
Finally, using the wrong conduit internal diameter for your specific conduit type matters. PVC Schedule 80 has a smaller ID than PVC Schedule 40 at the same trade size, and the difference increases with larger conduit sizes.
Pulling data cable only? See our Cat6 / Cat6a conduit fill calculator with data-cable OD specs built in.
When Derating Applies
When Derating Applies
While this calculator focuses on physical fill capacity, installers should also be aware of ampacity derating requirements that affect power-carrying conductors. When more than three current-carrying conductors are bundled in the same conduit, NEC Table 310.15(C)(1) requires derating the ampacity of each conductor to account for mutual heating. NEC Article 725 generally permits low-voltage circuits to share raceways with power circuits only under specific conditions.
The 60% fill allowance for conduit nipples (24 inches or shorter) applies only to short stub-ups and connections between adjacent boxes; it cannot be used for general conduit runs.
Temperature ratings also matter. Conductors in a conduit exposed to ambient temperatures above 86°F (30°C) require additional derating per NEC Table 310.15(B)(1).
Fire-Stopping Considerations
Fire-Stopping Considerations
Fire-rated pathways like STI EZPath and Hilti CFS modular sleeves serve a fundamentally different purpose than standard conduit. They maintain the fire rating of wall and floor penetrations while allowing cables to pass through. Their fill calculations are based on manufacturer testing and UL listings, not NEC Chapter 9 tables. This is why our calculator uses interpolated lookup tables from STI and Hilti rather than the standard area-based formula.
Overfilling a fire-rated sleeve compromises the fire barrier, potentially voiding the fire rating and creating a life-safety hazard. The intumescent material inside these devices needs adequate air space to expand properly during a fire.
Always follow the manufacturer's maximum cable count for the specific cable diameter you are installing, and maintain documentation of the fill for each penetration. Fire marshals and inspectors routinely verify fire-stop installations during building inspections.
For STI and Hilti fire-rated sleeves, see our dedicated fire sleeve fill calculator with UL-tested tables for EZPath and CFS-MSL.
Cable Jam Probability in Conduit
Cable Jam Probability in Conduit
Three cables of the same size can lock into a triangular wedge inside a conduit, jamming the pull permanently. This happens when the ratio of conduit ID to cable OD falls between 2.8 and 3.2, per NEC Chapter 9, Table 1, Informational Note 2. Peak jam probability occurs around 2.9 to 3.1. Below 2.8 the cables are too large to form the three-point contact geometry; above 3.2 they slide past each other freely.
This only affects exactly three identical cables. Four or more cables statistically cannot achieve the same locking geometry. Our Real World calculator checks this ratio automatically and flags runs in the danger zone.
If you hit the jam range, the fix is simple: go up one conduit trade size. A $0.30/ft conduit upgrade beats a $3,000 re-pull any day.
Pull Tension & Why Run Length Matters
Pull Tension & Why Run Length Matters
NEC fill percentages assume a perfect world where cables slide effortlessly into place. Real installations have friction, gravity, and bends working against you. Pull tension increases with run length, cable weight, number of cables, and every bend in the conduit.
The formula uses the capstan equation: tension multiplies exponentially with each bend. Two 90-degree bends don't double tension; they roughly triple it when friction is factored in. Dry conduit (friction coefficient around 0.50) creates dramatically more resistance than lubricated conduit (0.15-0.20 with gel lubricant).
For Ethernet cables, TIA-568 sets a hard limit of 25 pounds of pulling force. Exceed that and you risk stretching the twisted pairs, which kills crosstalk performance and can cause intermittent failures that are nearly impossible to diagnose.
Why Mixed Cable Fill Calculations Matter
Why Mixed Cable Fill Calculations Matter
Most conduit fill calculators only let you enter one cable type at a time. That works fine when you are pulling 24 Cat6 cables in a dedicated data conduit. It falls apart the moment you need to route Cat6 alongside fire alarm cables, or pull fiber and coax through the same sleeve. Real conduit runs regularly carry mixed cable bundles, especially in riser conduits, shared ceiling pathways, and fire-rated penetrations where you want to minimize the number of sleeves.
Static fill charts cannot handle mixed cables because each cable type has a different outside diameter, and the NEC area-based formula must account for each one individually. A conduit that passes at 38% fill with twelve Cat6 cables fails at 44% when you add four 14/2 fire alarm cables.
The only way to get an accurate fill percentage for a mixed bundle is to sum the individual cable areas and compare against the conduit's internal cross-section. This calculator supports up to five different cable types per calculation, making it the only free tool that handles real-world mixed conduit fills correctly.
Mixing data, fire alarm, access control, and fiber? Try our low-voltage conduit fill calculator built for mixed cable runs.
Real-World Install Examples
Three commercial install scenarios where the fill math made the call. All numbers below use the same NEC Chapter 9 rules and manufacturer cable ODs built into the calculator above — plug them in to reproduce the result.
Office Building — Cat6a in 3/4" EMT Stub-Ups
Commercial office build-out. The EC installed 3/4" EMT stub-ups at every data location during rough-in. Customer specified Cat6a.
| Cable Count | Fill % | NEC Result |
|---|---|---|
| 1 × Cat6a UTP (0.300" OD) | 13.3% | PASS |
| 2 × Cat6a UTP | 26.5% | PASS |
| 3 × Cat6a UTP | 39.8% | PASS (at the limit) |
| 4 × Cat6a UTP | 53.0% | FAIL |
The call:We capped each 3/4" stub at 2 Cat6a cables. Three passes the math at 39.8%, but a slightly thicker manufacturer-tolerance jacket pushes you over. Locations needing more than 2 cables got re-piped to 1" EMT during rough-in.
The lesson:Two cables is the safe rule of thumb for 3/4" EMT + Cat6a. Don't fight the gray area — if you need a third drop, upsize the pipe.
Medical Office — 1" Sleeves Trying to Carry 10+ Cat6a
100-room medical office. The EC installed a single 1" EMT sleeve per room. Several rooms needed 10+ Cat6a drops for patient devices, exam-room workstations, and access readers.
| Cable Count | Fill % | NEC Result |
|---|---|---|
| 4 × Cat6a UTP (0.300" OD) | 32.7% | PASS |
| 5 × Cat6a UTP | 40.9% | FAIL |
| 10 × Cat6a UTP | 81.8% | FAIL — 2× the limit |
The call:Four Cat6a UTP is the max in a 1" sleeve at the NEC 40% rule. Trying to stuff 10 into a 1" pipe isn't borderline — it's twice the legal limit.
The lesson:Instead of arguing "but it fits!" with the EC, take it to the math. NEC 40% is non-negotiable. The fix: add a second 1" sleeve per room, or upsize to 1-1/4" EMT (fits ~7 Cat6a UTP at 33.2%).
Hospital Pharmacy — 4 × 4" RMC Sleeves for Cat6a
Hospital pharmacy build-out. The EC bid four 4" RMC sleeves total, claiming "all the Cat6a will fit." Physically it would have — but physically isn't the same as code-compliant.
| Cable Count | Fill % | NEC Result |
|---|---|---|
| 50 × Cat6a UTP (per pipe) | 24.0% | PASS |
| 75 × Cat6a UTP | 36.0% | PASS |
| 83 × Cat6a UTP | 39.8% | PASS (last safe count) |
| 84 × Cat6a UTP | 40.3% | FAIL |
| 100 × Cat6a UTP | 47.9% | FAIL |
The call:A 4" RMC pipe legally holds ~83 Cat6a UTP cables. If the project needed 400+ cables (≈100 per pipe across four), four pipes aren't enough — that's a code violation, not just a tight fit.
The lesson:Low voltage isn't exempt from NEC fill rules. NEC Chapter 9 and NFPA 70 apply the same 40% rule to us as they do to power conductors. The calculator turns "it'll fit" into "here's the percentage" — and the math wins every argument.
Why we built one tool for EMT, Hilti, and STI EZPath
Field crews used to bounce between NEC Chapter 9 Table 1 for standard sleeves, the Hilti CFS-MSL spec sheet for speed sleeves, and the STI EZPath datasheet for fire-rated transitions — three different sources for what should be one calculation. We built the fill tables for all of them (plus EMT, RMC, IMC, PVC Sch40/80, ENT, LFNC, and LFMC) into a single calculator so the answer is one click away, not three browser tabs deep. The fill numbers above match the manufacturer-published values — verify against the source datasheets anytime if a project requires AHJ-grade documentation.
Frequently Asked Questions
NEC Article 300.3(C)(1) generally prohibits mixing power and low-voltage cables in the same raceway unless all conductors are rated for the highest voltage present. In practice, low-voltage (Cat6, fire alarm) and line-voltage (THHN) almost always require separate conduits. This calculator lets you model each conduit independently so you can plan parallel runs and correctly size both raceways for their respective cable bundles.
NEC 344.26 limits conduit runs to 360 degrees of total bends between pull points. While bends don't change the fill percentage calculation, they dramatically increase pulling tension and jam probability. If your run has three or more 90-degree bends, consider upsizing the conduit one trade size beyond what the fill calculation recommends. This calculator shows you the next recommended size, which is particularly useful when planning runs through tight ceiling spaces or riser shafts.
NEC Chapter 9, Note 4 allows 60% fill for conduit nipples 24 inches or shorter — compared to 40% for three or more conductors in standard runs. This is critical in telecom rooms where you're stubbing short runs between wall-mounted backboards and ceiling J-hooks, or between adjacent rack cabinets. Use the short nipple allowance in this calculator to avoid oversizing conduit for these short transitions and save on material costs.
BICSI and TIA-568 standards recommend filling conduit to no more than 50-60% of the NEC maximum to leave headroom for future pulls. In this calculator, add your current cable count plus your estimated future cables (typically 25-50% more for a 5-year growth plan), then size the conduit for that total. A 1" EMT that passes at 38% today will fail when the tenant next door needs 12 more Cat6a drops routed through the same pathway.
Fire-rated pathway systems have unique internal geometries that differ significantly from standard round conduit. An STI EZPath 2-gang device has a rectangular opening with different fill characteristics than a 2" EMT. This calculator includes specific fill tables for STI EZPath and Hilti fire-rated sleeves, accounting for their actual internal dimensions rather than approximating them as round conduit. This prevents both undersizing (fire code violation) and oversizing (unnecessary cost) at fire-rated penetration points.
There are several scenarios where upsizing beyond the minimum NEC requirement is smart practice. If you're pulling cables longer than 100 feet, have more than two 90-degree bends, using cables with thick jackets (like Cat6a or plenum-rated), or working in hot ceiling environments where cable expansion matters, go up one trade size. Also, if your calculated fill is between 35-40% with three or more conductors, you're right at the threshold — one miscalculated cable OD could push you over. This calculator shows your exact percentage so you can make an informed decision.
This page includes both. Scroll below the calculator to find our static THHN conduit fill chart showing maximum conductor counts per conduit size for 14 AWG through 1 AWG across EMT, RMC, PVC Sch40, and PVC Sch80 — sourced directly from NEC Chapter 9 Table C. Switch to Low Voltage mode for a separate low-voltage conduit fill table covering Cat5e, Cat6, Cat6a, and fire alarm cables computed from manufacturer OD data at 40% fill. Both tables are free to reference anytime without running a calculation.
The conduit size depends on three factors: the number of cables, each cable's outside diameter (OD), and the conduit type. For example, twelve Cat6 cables (0.25" OD each) need at least 3/4" EMT at 39% fill, but twelve Cat6a cables (0.30" OD each) push you to 1" EMT. This conduit size calculator automatically recommends the smallest compliant conduit when your selected size fails. Enter your cable mix, and if the fill exceeds the NEC limit, the tool shows the next trade size that passes. For mixed cable bundles, the area-based calculation is the only reliable method, as static conduit fill tables only cover single conductor types.
TSS USA. (2025). NEC Conduit Fill Calculator. Retrieved from https://tssusa.net/conduit-fill-calculator/
<a href="https://tssusa.net/conduit-fill-calculator/" title="NEC Conduit Fill Calculator by TSS USA">NEC Conduit Fill Calculator - TSS USA</a>Last Updated: June 1, 2025
Calculations follow NEC Chapter 9, Table 4 fill rates and NFPA 70 standards. Wire outside diameter data sourced from manufacturer specifications. Fire-rated pathway capacities use interpolated lookup tables from STI and Hilti published data.
Standards & References
- NFPA 70 — National Electrical Code (NEC) — Chapter 9, Tables 1 & 4 — conduit fill limits and internal dimensions
- NEC Chapter 9, Table C1 — Maximum conductor fill for EMT conduit
- BICSI — Low-voltage cabling standards and best practices
Try Our Other Calculators
Cable Price Estimator
Instant ballpark pricing for structured cabling projects.
Phone System Cost Guide
Cloud VoIP vs on-premise PBX cost breakdown with line-item estimates.
Voltage Drop Calculator
Verify the voltage at the device end of an existing wire run.
Wire Sizing Calculator
Pick the smallest AWG that passes NEC 310.16 ampacity, derating, and drop.
Paging Design Tool
Visual paging system designer with PDF floor plans and wire sizing.
Fire Alarm Battery Calculator
NFPA 72 battery sizing and NAC voltage drop with real device data.
EMT Conduit Fill Calculator
EMT-specific fill calculator with NEC Table C1 chart.
PVC Conduit Fill Calculator
PVC Schedule 40 & 80 fill calculator with NEC Tables C10/C11.
Cat6 Conduit Fill Calculator
Data cable fill calculator for Cat5e, Cat6, Cat6a, and Cat8.
Low Voltage Conduit Fill
Fill calculator for fire alarm, access control, ethernet, and fiber.
Fire Sleeve Fill Calculator
Cable fill for Hilti Speed Sleeves, Modular Sleeves, and STI EZ Path.
Cable Tray Fill Calculator
NEC 392 fill calculator for ladder, ventilated, and solid-bottom cable trays.
Add This Calculator to Your Site
Give your readers a free NEC-compliant conduit fill tool without building one. Covers THHN, Cat6, Cat6a, fire alarm, and low-voltage cables in EMT, PVC, and RMC. Built by licensed low-voltage professionals. Trusted by contractors across Florida.
One paste. No account. No fees. Works on any page — WordPress, Squarespace, Webflow, or plain HTML. The calculator is hosted on our end so it always stays current.
Electrical Training Sites
Give students a live NEC reference tool
Trade Blogs & Forums
Add utility to your conduit sizing articles
Contractor Resource Pages
Save your team from manual fill calculations
<iframe
src="https://tssusa.net/conduit-fill-calculator/"
width="100%"
height="900"
style="border:none;border-radius:8px;"
title="Free NEC Conduit Fill Calculator — TSS USA"
loading="lazy"
allowfullscreen>
</iframe>
<p style="font-size:12px;color:#888;margin-top:6px;">
Free NEC conduit fill calculator by
<a href="https://tssusa.net/conduit-fill-calculator/"
target="_blank" rel="noopener">TSS USA</a>
</p>