AC voltage drop sizes the right conductor for the run. NEC 210.19(A) caps branch-circuit drop at 3%; NEC 215.2(A) caps feeder + branch combined at 5%. Both are Informational Notes — not enforceable code text — but most AHJs treat them as required for permit approval. This calculator runs the math against NEC Chapter 9 Table 9 impedance values, handles single and three-phase, factors in power factor and aluminum vs copper, and flags every result as pass or fail against the threshold you set.
Estimates based on NEC, NFPA, and IEEE standards. For reference only. Consult a licensed professional for critical design decisions.
Enter one-way distance — we calculate the round trip automatically.
Select inputs & calculate
NEC AC Voltage Drop Limits
Default thresholds for branch and feeder circuits
Branch Circuit
NEC 210.19(A) Informational Note
Feeder + Branch
NEC 215.2(A) combined max
Motor Starting
NEMA MG-1 in-rush window
Power Factor
Default for motor loads
AC Voltage Drop in the Real World
What NEC actually requires, what your AHJ enforces, and where the numbers come from.
NEC 210.19 vs 215.2 — What the Code Actually Says
NEC 210.19 vs 215.2 — What the Code Actually Says
NEC Article 210.19(A) Informational Note No. 4 recommends branch circuits not exceed 3% voltage drop at the farthest outlet. NEC 215.2(A)(1) Informational Note No. 2 caps feeders at 3%, with combined feeder + branch drop at the farthest outlet capped at 5%. Both are Informational Notes — they are not enforceable code text. But most AHJs treat them as required for permit approval, and most engineers design to them as a hard rule. The math: a feeder that runs at 2.5% leaves only 2.5% available for the branch.
Single-Phase vs Three-Phase Math
Single-Phase vs Three-Phase Math
Single-phase voltage drop uses Vdrop = 2 × I × Z × L, where the factor of 2 accounts for round-trip current through hot and neutral. Three-phase uses Vdrop = √3 × I × Z × L (about 1.732 instead of 2) because in a balanced three-phase system, current returns through the other two phases instead of a dedicated neutral. For the same load and distance, three-phase drop is about 13% lower than single-phase — one reason large feeders and motor branch circuits run three-phase wherever practical.
Copper vs Aluminum — Where the Tradeoff Lives
Copper vs Aluminum — Where the Tradeoff Lives
Copper has roughly 60% more ampacity per cross-sectional area than aluminum. A 4/0 aluminum service feeder is functionally equivalent to a 2/0 copper feeder for most loads. Aluminum is cheaper per pound, lighter, and standard for most commercial and residential service feeders. Copper is required for branch circuits in most jurisdictions and is the default for any short, high-current run where mechanical fatigue or thermal cycling is a concern. Critical: aluminum requires antioxidant compound on terminations, aluminum-rated lugs, and proper torque specs — bad aluminum terminations cause more service-call fires than any other code violation.
Power Factor — Why 0.85 Is the Default
Power Factor — Why 0.85 Is the Default
NEC Chapter 9 Table 9 publishes effective Z values at 0.85 power factor. That covers most real-world loads — motors, lighting ballasts, transformer-coupled equipment. For pure resistive loads (electric heat strips, incandescent lighting, baseboard heaters), use PF = 1.0 because there is no inductive reactance and the impedance equals pure resistance. For loads with poor power factor (older fluorescent ballasts, induction motors, large HVAC compressors), PF can drop to 0.7 — the calculator lets you set this manually.
Motor Circuits and Starting Current
Motor Circuits and Starting Current
A motor running at 30A may pull 180-240A locked-rotor for 0.5-1 second on start-up. A circuit that calculates pass at 3% running drop may experience 18-24% drop during start-up — enough to trip overcurrent protection, stall the motor, or burn out a contactor. NEMA MG-1 requires motors to operate within ±10% of nameplate voltage at full load. For motor circuits, run two calculations: running drop (use the standard tool inputs) and locked-rotor in-rush drop (multiply the running current by 6-8x). If start-up drop exceeds 10%, increase wire size or shorten the run.
Feeder Sizing — the Subpanel and EV Charger Story
Feeder Sizing — the Subpanel and EV Charger Story
Subpanel feeders are where AC voltage drop catches contractors off guard. A 100A subpanel fed 150 feet from the main panel on 1/0 aluminum will calculate around 2.8% at full load — fine until you add an EV charger to the subpanel. The 32A charger pulls continuously for hours, and the combined feeder + branch drop at the EVSE outlet can push past 5%, which slows charging and can trip the charger. Calculate the worst-case continuous load, not just the panel rating.
Long Runs and Outdoor Lighting
Long Runs and Outdoor Lighting
Parking lot lighting, monument lighting, and outdoor signs frequently sit 200-400 feet from the panel. At 277V single-phase on 12 AWG copper, a 200ft run carrying 12A drops about 4.2V — over 1.5%. Run that to 400ft, and you are at 3% before the lights even turn on. For long runs, step up to 10 AWG or 8 AWG, or step the supply voltage up to 480V where available. The math doesn't care how far the cable goes; the percentages just compound.
Temperature Derating in AC Calculations
Temperature Derating in AC Calculations
Copper resistance climbs about 0.4% per °C above 75°C reference. Aluminum is similar. Conduit in direct sun in Florida can reach 60°C ambient; rooftop runs can hit higher. Underground branch circuits in deep cold (Northern winters) actually have lower resistance and pass more easily. The calculator handles temperature derating both directions, so you can model worst-case-day conditions for any installation.
For DC circuits, see the DC voltage drop calculator tuned for 12V, 24V, and 48V. To find the smallest gauge that passes both ampacity and voltage drop checks at once, use the wire sizing calculator. For other applications, use the multi-mode voltage drop calculator.
Frequently Asked Questions
For single-phase AC, the formula is Vdrop = 2 × I × Z × L, where I is current in amps, Z is conductor impedance per foot from NEC Chapter 9 Table 9, and L is one-way distance in feet. The factor of 2 accounts for the round-trip path through the hot and neutral. Power factor adjustments matter for inductive loads (motors, fluorescent ballasts) — multiply the drop by the power factor (typically 0.85 for motors, 1.0 for resistive loads like incandescent or strip heaters). This calculator runs that math for you with NEC-published values.
Three-phase uses Vdrop = √3 × I × Z × L instead of the factor of 2. Why? Because in a balanced three-phase system, current returns through the other two phases rather than a dedicated neutral, and the geometry of the phase angles produces the √3 multiplier (about 1.732). At the same current and distance, three-phase drop is about 13% lower than single-phase, which is one reason large feeders and motor circuits run three-phase whenever practical. This calculator handles single and three-phase automatically when you toggle the phase selector.
Per NEC 210.19(A) Informational Note, branch circuits should not exceed 3% drop. Per NEC 215.2(A), feeders should not exceed 3%, AND the combined feeder + branch drop at the farthest outlet should not exceed 5%. So if your feeder runs at 2.5%, your branch can only run 2.5% to keep the combined under 5%. The 3%/5% rule is a recommendation, not enforceable code, but most AHJs treat it as required for permit approval. Sensitive loads (audio gear, sensitive electronics, hospital instrumentation) target tighter — 1% to 2%.
It depends entirely on amperage and gauge. Roughly: 12 AWG copper at 20A drops about 1.0V per 100 feet on a 240V single-phase circuit (0.4%). 10 AWG at 30A drops about 0.95V per 100 feet. Larger conductors at higher current can run 4-8V per 100 feet. The 3% rule says you can lose up to 7.2V on a 240V circuit before it becomes a problem — but use the calculator on your specific job rather than rules of thumb.
7.2V maximum on the branch (3% of 240V), or 12V combined feeder + branch (5%). For dwelling unit service feeders running at full load, 5% is the hard ceiling. For sensitive loads on a 240V circuit — for example, a TIG welder, a CNC machine, or audio gear — designers often target 2% (4.8V max) to avoid performance issues from sag during heavy loads. Note: the percentages are calculated against nominal voltage at the source, not the actual measured voltage at the panel.
Copper has roughly 60% more current-carrying capacity per area than aluminum, so a 4/0 aluminum feeder is roughly equivalent to a 2/0 copper. Aluminum is cheaper per pound and lighter, which is why most service feeders to commercial buildings are aluminum. Copper is required for branch circuits in most jurisdictions and for any installation where mechanical fatigue or thermal cycling is a concern (panel-to-disconnect short feeders, motor circuits with frequent starts). Aluminum requires antioxidant compound on terminations and torque-spec connections; aluminum-rated lugs are mandatory.
Yes — for inductive loads, the impedance affects voltage drop differently than pure resistance. Motors, transformers, fluorescent and HID lighting, and electronic ballasts have power factors below 1.0 (typically 0.7 to 0.9). NEC Chapter 9 Table 9 publishes effective Z values at 0.85 power factor as the default. If your load has a different PF, multiply the drop by your actual PF for a more accurate result. For purely resistive loads (resistance heaters, incandescent lighting, baseboard heat), use PF = 1.0.
NEC 2026 keeps the 3% branch / 5% combined recommendations as informational notes (210.19 and 215.2). What did change: 210.19(A)(2) added explicit language about EV charging branch circuits, and 215.12 expanded feeder marking requirements. The voltage drop math is unchanged — same Chapter 9 Table 9 impedance values. Most state code adoptions are 2-3 years behind, so check your AHJ for which NEC cycle they enforce.
Running voltage drop and starting voltage drop are different problems. NEMA MG-1 specifies motors must operate within ±10% of nameplate voltage at full load. Starting in-rush can hit 6-8× running current for 0.5-1 second. A motor circuit that calculates pass at 3% running may see 18-24% drop during start-up, which can trigger overload trips, stall the motor, or burn out a contactor. For motor circuits, calculate both running drop (use the calculator) and locked-rotor in-rush drop separately. Increase wire size or shorten the run if start-up drop exceeds 10%.
TSS USA. (2026). AC Voltage Drop Calculator. Retrieved from https://tssusa.net/ac-voltage-drop-calculator/
<a href="https://tssusa.net/ac-voltage-drop-calculator/" title="AC Voltage Drop Calculator by TSS USA">AC Voltage Drop Calculator - TSS USA</a>Last Updated: May 6, 2026
Calculations derive from NEC Chapter 9 conductor data with DC resistance values published at 20°C reference. Single-phase formula: Vdrop = 2 × I × R × L × PF. Three-phase formula: Vdrop = √3 × I × R × L × PF. Power factor adjustments apply to inductive loads (motors, ballasts). Aluminum conductor resistance values per NEC Table 8 (~1.6× copper for the same gauge). Temperature correction uses copper's standard coefficient (α = 0.00393/°C) applied between ambient temperature and the 20°C reference. Threshold defaults reference NEC 210.19(A) and 215.2(A) Informational Notes.
Try Our Other Calculators
Conduit Fill Calculator
NEC-compliant conduit fill for EMT, RMC, PVC, and fire-rated pathways.
Cable Price Estimator
Instant ballpark pricing for structured cabling projects.
Phone System Cost Guide
Cloud VoIP vs on-premise PBX cost breakdown with line-item estimates.
Voltage Drop Calculator
Verify the voltage at the device end of an existing wire run.
DC Voltage Drop Calculator
12V, 24V, 48V circuits. Solar, marine, RV, access control, low-voltage installs.
Fire Alarm Voltage Drop Calculator
NFPA 72 NAC point-to-point math, mixed candela strobes, battery standby mode.
Wire Sizing Calculator
Pick the smallest AWG that passes NEC 310.16 ampacity, derating, and drop.
Paging Design Tool
Visual paging system designer with PDF floor plans and wire sizing.
Fire Alarm Battery Calculator
NFPA 72 battery sizing and NAC voltage drop with real device data.
Cable Tray Fill Calculator
NEC 392 fill calculator for ladder, ventilated, and solid-bottom cable trays.
