DC voltage drop scales sharply at low system voltages. A 0.5V drop on a 120V branch is 0.4% — a non-event. That same 0.5V drop on a 12V camera or LED circuit is 4%, enough to brown out a long-run dome under IR load or visibly dim the end of a strip. This calculator runs copper resistance from NEC Chapter 9 Table 8, factors in temperature derating and CCA correction, and tells you whether your gauge passes across 12V, 24V, 48V, or any custom DC voltage.
Estimates based on NEC, NFPA, and IEEE standards. For reference only. Consult a licensed professional for critical design decisions.
Enter one-way distance — we calculate the round trip automatically.
Select inputs & calculate
DC Voltage Drop Thresholds
Use these as starting points. Adjust for your install.
Strict
Sensitive electronics
Audio, control, instrumentation
Standard
Most low-voltage installs
Cameras, access control, LED lighting
Acceptable
Solar / off-grid / RV
Battery bank to inverter, accessories
Mag Lock Limit
SDC / manufacturer max
Below this, locks may not release
DC Voltage Drop Field Guide
What actually matters in 12V, 24V, and 48V wiring decisions.
Why Drop Hurts More at Low Voltage
Why Drop Hurts More at Low Voltage
Voltage drop is a percentage of the source. Same 0.5V loss is 0.4% on 120V AC and 4% on 12V DC. That's why a circuit that "would never matter" on the AC side becomes a make-or-break decision on a 12V solar accessory run, a 24V mag lock circuit, or a 48V battery-to-inverter cable. The cable doesn't get any worse — the math just bites harder.
Picking a Threshold That Fits Your Job
Picking a Threshold That Fits Your Job
3% for sensitive electronics (audio amps, instrumentation, control circuits). 5% for most low-voltage trade work — cameras, access control, LED panels, landscape lighting. 10% is acceptable for off-grid solar and RV/marine accessory loads where battery cycling efficiency is the bigger concern. Mag locks have their own ceiling: keep drop under 12% so the lock holds and releases cleanly.
CCA vs Solid Copper — the 60% Penalty
CCA vs Solid Copper — the 60% Penalty
Copper-clad aluminum (CCA) cable has roughly 55–60% higher resistance than solid copper of the same AWG. It tests fine for connectivity but starves devices under load. CCA is common on bargain pre-terminated patch cables and unbranded reels — the kind that show up on a job site without a manufacturer name. For battery-to-inverter or any high-current DC run, CCA is dangerous: under continuous high amperage, the conductor heats up faster than copper and the insulation can fail. Don't use CCA on critical DC.
Daisy-Chain vs Home-Run Topology
Daisy-Chain vs Home-Run Topology
Most DC circuits are home-run (one cable per device). Some are daisy-chained — multiple mag locks on one PSU output, multiple LED fixtures on a shared trunk, multiple devices on one battery bank pair. The math is different: in a daisy chain, the cable from the source carries the cumulative current of all downstream devices, so the segment closest to the source gets hit hardest. The calculator's multi-device mode handles this correctly; the worst-case voltage is at the device farthest from the source.
Temperature Derating — the Florida Tax
Temperature Derating — the Florida Tax
Copper resistance climbs about 0.4% per °C above 75°C reference. Outdoor cable in a Tampa Bay attic can hit 60°C easily; conduit in direct sun runs higher. RV and marine cables routed near engines or in unventilated battery compartments see the same penalty. A run that calculates pass at 25°C may marginal-or-fail at 60°C. Use the temperature input to model worst-case-day performance, especially on cameras and outdoor accessory circuits.
When to Upsize vs When to Shorten
When to Upsize vs When to Shorten
If the cable route is fixed, upsizing is your only move. 14 AWG to 12 AWG cuts resistance ~37%. 16 to 12 cuts it ~60%. If equipment placement is flexible, shortening is almost always cheaper than thicker copper — pulling a camera PSU 30 feet closer to the camera cluster solves the problem without buying heavier wire. Battery-to-inverter is the exception: shortening usually isn't possible, so gauge does all the work.
Need a different calculation? Try the multi-mode voltage drop calculator for PoE, fire alarm NAC, access control, or AC circuits — or our wire sizing calculator if you want to find the smallest gauge that passes both ampacity and voltage drop checks at once.
Frequently Asked Questions
For battery bank to inverter runs, 3% is the smart target — that's the line where your inverter still has clean DC under load and your battery isn't doing extra work to compensate. 5% is acceptable on shorter accessory runs (lights, fans, fridge). Anything past 10% on a 12V system means real losses you'll feel as dim lighting, undersized inverter output, and shortened battery cycle life. The math is unforgiving at 12V because every 0.12V is another 1%.
Battery-to-inverter runs carry the highest current in the whole system, often 100A+ at full load. Use the calculator with the inverter's peak DC input current (continuous watts ÷ 12V), the round-trip distance, and a 3% threshold. For a 2000W inverter at 12V, that's ~167A continuous on copper that needs to be 2/0 AWG or larger for a 5-foot run. CCA is not acceptable here — under that current, it overheats and fails. Use only fine-stranded marine-grade copper.
You're hitting voltage drop. LED strips draw current along their full length, so the LEDs near the power supply see ~12V and the LEDs at the far end see whatever's left after resistance eats the rest. A 16-foot run of 22 AWG strip at 4A pulls roughly 0.8V on the wire — that's enough to visibly dim the end. Fix: feed power to both ends, or run a heavier 12-volt pair to the midpoint, or step up to a 24V strip system that tolerates drop better.
For DC voltage drop, no — stranded and solid copper of the same AWG have effectively the same resistance per foot. The "use stranded for flex, solid for fixed runs" rule is about mechanical fatigue and termination, not electrical performance. Where the math does change is CCA (copper-clad aluminum) versus solid copper: CCA carries roughly 55–60% more resistance for the same gauge, which on a 12V circuit can push a passing run into failing territory.
Yes, but the math matters. When 4 cameras share one 18 AWG home-run, the cable carries the total current of all 4 cameras (~3A combined for typical IR domes) plus the round-trip distance. The cable's resistance acts on the cumulative current, so the run that passed for one 0.7A camera will fail for four. Use the calculator's multi-device mode to model the actual cumulative drop, or split the cameras across separate home-runs if you're close to the threshold.
Most 600 lb mag locks pull 0.5A continuous; 1200 lb locks pull 0.75A. With 18 AWG stranded copper at 0.5A and a 5% threshold (0.6V max drop), the practical limit is around 95 feet one-way. Switch to 16 AWG and you get to ~150 feet. Past that, run 14 AWG or move the power supply closer. Critical detail: if your AHJ requires the lock to release within a specific time after fire alarm trip, the voltage at the lock matters not just for hold but for clean release timing.
Copper resistance climbs about 0.4% for every degree Celsius above the 75°C reference. Cable in a Florida attic in August can sit at 60°C ambient, which is roughly 14% higher resistance than the spec sheet shows. The calculator includes a temperature input so you can model worst-case-day performance — for outdoor security camera runs, conduit in direct sun, or RV/marine cables routed near engines, it's the difference between a passing calc and an unexpected brownout.
If the cable path is fixed (existing conduit, building layout, conduit fill limits), upsizing is your only lever. Going from 14 AWG to 12 AWG cuts resistance by ~37%. Going from 16 to 12 cuts it by 60%. If you have flexibility in equipment placement, shortening the run is almost always cheaper than thicker cable — moving a camera PSU 30 feet closer to the cluster eliminates the problem without buying heavier gauge. For battery-to-inverter, shortening is rarely an option, so wire size carries the whole load.
TSS USA. (2026). DC Voltage Drop Calculator. Retrieved from https://tssusa.net/dc-voltage-drop-calculator/
<a href="https://tssusa.net/dc-voltage-drop-calculator/" title="DC Voltage Drop Calculator by TSS USA">DC Voltage Drop Calculator - TSS USA</a>Last Updated: May 6, 2026
Calculations use copper DC resistance values published at 20°C reference, derived from NEC Chapter 9 Table 8. Round-trip drop formula: Vdrop = 2 × I × R × L. CCA cable resistance adjusted by 1.55× per published manufacturer test data. Temperature correction uses copper's standard coefficient (α = 0.00393/°C) applied between ambient temperature and the 20°C reference. Multi-device cumulative drop calculated per-segment with downstream current summation, matching real-world daisy-chain installations on access control PSU circuits and shared 12V camera runs.
Try Our Other Calculators
Conduit Fill Calculator
NEC-compliant conduit fill for EMT, RMC, PVC, and fire-rated pathways.
Cable Price Estimator
Instant ballpark pricing for structured cabling projects.
Phone System Cost Guide
Cloud VoIP vs on-premise PBX cost breakdown with line-item estimates.
Voltage Drop Calculator
Verify the voltage at the device end of an existing wire run.
AC Voltage Drop Calculator
Single and three-phase, NEC 210.19 / 215.2 compliance, copper and aluminum.
Fire Alarm Voltage Drop Calculator
NFPA 72 NAC point-to-point math, mixed candela strobes, battery standby mode.
Wire Sizing Calculator
Pick the smallest AWG that passes NEC 310.16 ampacity, derating, and drop.
Paging Design Tool
Visual paging system designer with PDF floor plans and wire sizing.
Fire Alarm Battery Calculator
NFPA 72 battery sizing and NAC voltage drop with real device data.
Cable Tray Fill Calculator
NEC 392 fill calculator for ladder, ventilated, and solid-bottom cable trays.
